How to check dynamic water pressure with AquaScan?

  • Connect AquaScan to the outlet.
  • Fully open the isolation valve on the outlet of the unit.
  • Open the outlet and allow flow through the unit until the desired flow rate is reached.
  • Take three measurements from the live ‘Pressure’ reading. Calculate the average of the three measurements.
  • Turn off the outlet.

Note: the pressure should always read “0.0” before removing the unit from the outlet.