How to check dynamic water pressure with AquaScan?
- Connect AquaScan to the outlet.
- Fully open the isolation valve on the outlet of the unit.
- Open the outlet and allow flow through the unit until the desired flow rate is reached.
- Take three measurements from the live ‘Pressure’ reading. Calculate the average of the three measurements.
- Turn off the outlet.
Note: the pressure should always read “0.0” before removing the unit from the outlet.